8000159 - Hybrid Modbus Gateway (ext. Power, Din-Rail) Including: Antenna | 8000166 - Hybrid Modbus Gateway (ext. Power, 230V) Including: Antenna, 2x cable feedthrough | 8000171 - Hybrid Modbus Gateway V2 (Battery) |
Table of Content
Table of Contents | ||
---|---|---|
|
Overview
The Lobaro Hybrid Modbus Gateway is a simple to use, cost and energy efficient device that reads, caches and forwards data via Modbus from any number of Modbus enabled devices into the Internet.
...
The Modbus Gateway supports reading of all four object types that can be provided by Modbus slave devices: Coil, Discrete Input, Input Register, and Holding Register. It also supports writing values to all writable objects: Coils and Holding Registers. Multiple different slave devices on the Bus can be accessed individually by a single Gateway device, even if the slave devices have a different Modbus configuration. Reading intervals and register definitions can be configured very flexibly to suit individual requirements.
Quick start guide
For details about each Steps please refer to the related detailed sections of the Manual below.
- Make sure the SIM card is inserted correctly when using NB-IoT or LTE-CatM1.
- Connect the Modbus Gateway to your Modbus Slave Devices
- Via RS485 connector using a twisted pair cable:
A
toA
,B
toB
, andGND
toGND
(GND
is not strictly necessary but enhances the connection. Not all slave devices supply aGND
connector). - Via ETH connector for Modbus TCP using a RJ45 LAN cable(externally powered variants only).
- Via RS485 connector using a twisted pair cable:
- Connect the Modbus Bridge to a computer using the Lobaro Configuration Adapter and the Lobaro Maintenance Tool.
- Connect power to the device - powering with the configuration adapter does not work.
- Make sure the configuration is correct to connect to the Internet (depends on you connection method: Mobile, LoRaWAN or LAN.
- Make sure the configuration is correct to read out your desired Modbus device (e.g. ASCII/RTU, Baud, Data Length, Stop Bits, Parity and Modbus Command).
- Optionally: Switch to the Log tab of the Lobaro Tool to see if the device is connecting and working as expected.
- Go to The Lobaro Platform and log into your account.
- Go to "Devices" and select your "Hybrid Modbus Gateway".
- If you have several Gateways: the "Address" is printed on the device's case as "DevEUI".
- You should see all Uplinks the Gateway collected sent far. Next step is to configure your individual Device Type to display you slaves data or forward data to your own IT.
Supported Devices
The Lobaro Modbus Gateway works with all devices that act as a Modbus Client using RTU, ASCII (or, in a future release TCP). Some devices that have been used successfully with the Gateways are:
Device | Type | Manufacturer | More information | Sample Implementations |
---|---|---|---|---|
Octave Ultrasonic Meter | Water meter | Arad Group | External Link | |
ECL Controller | Heat/Hot Water Regulation | Danfoss | External Link | |
UMD 97 | Smart Grid Power Meter | PQ Plus | External Link (German) | |
DRS458DE | Power Meter | B+G E-Tech GmbH | External Link | |
Feuchtemessumformer PCE-P18 Modbus RTU | Humidity / Temperature sensor | PCE-Intruments | External Link (German) | |
Lobaro Pressure Sensor | Pressure Sensor | Lobaro | Sample Implementations |
Modbus Introduction
For an overview about the Modbus protocol please refer to our documentation page about Modbus.
...
Info |
---|
Please be aware that to configure the Gateway correctly, you will need to know the details of your installation and the slave devices you are trying to connect. Debugging a failing Modbus setup is quite complex, as there are many potential errors that cause the problems. Please also note that even when you succeed in reading the data you need from the correct registers, neither the Gateway, nor the Lobaro Platform can know, what that data means. There is no semantic defined in Modbus; without additional information, the data is just bytes, that need to be interpreted by custom software. Registers can hold boolean values, signed or unsigned integers, floating point numbers or anything else. Often values span over multiple registers (each register holds exactly 2 bytes, so that e.g. 32bit integers will need two registers. There is also no dedicated byte order for Modbus, so that is not even trivial to read integers. This is a problem that is intrinsic to using Modbus and cannot be solved easily by a generic bridge device. If you need support for creating a custom parser that processes the Uplinks and convert it to an easy to use format, please contact us, so that we can send you an offer for your individual use case. |
Setting up the device
Interfaces
Connections as on the label:
...
Note |
---|
|
Power Supply
- Power supply via external mains adapter with 12 - 24 Volt DC
- Power output must be at least 2W and maximum 100W.
Radio (LoRa, FSK, NB-IoT, LTE Cat-M1)
Female SMA Connector | Antenna | Nano SIM (4FF) for mobile connectivity |
...
Note |
---|
The SIM Card must not be inserted or removed while the device is powered. |
Properties of compatible SMA Antennas:
SMA Joint Rod Antenna (LTE, LoRa) | |
---|---|
Frequency range | 698-960 / 1710-2700 MHz |
Length | 108 mm |
Antenna Gain | 2 dBi |
V.S.W.R | <= 2.5 |
Radiation | Omnidirectional |
Polarisation | Vertical |
Max. Power | 5 W |
Impedance | 50 Ohm |
Connector | SMA Male |
Material of dome | TPE |
Lobaro Article No. | 3000413 |
...
Note |
---|
The device was only tested with the listed antenna. Lobaro does not take liability for use with different antennas. |
RESET-Button
- Press the RESET Button to restart the device
- The RESET Button can be pressed through a small hole in the cover (e.g. with a paper clip). The position is marked with a ring on the label.
Config Port
- The config port can only be reached when the cover is removed
- The configuration port is compatible with our 6-pin Lobaro USB Configuration Adapter (Article No. 8000005).
- A free to use configuration tool can be downloaded from the Lobaro website.
LED
- Status information is visualized via the RGB LED
Mobile operator and LTE band configuration
If you are using a different mobile operator than pre-configured, you should change the mobile operator code set in the Config Parameters Operator
and (LTE) Band
Operator codes are 5 digit codes that indicate country and operator.
Info |
---|
For details about configuration for mobile network operation please refer to our article about LTE Signal Strength Metrics |
Configuration
The device is shipped with default configuration parameters. The configuration can be changed via the 6-pin config port using the Lobaro USB Configuration Adapter.
...
Info |
---|
Remote Configuration is also supported after initial network connection. |
Networking Parameters (NB-IoT / LoRaWAN)
Name#LoRaWAN-RemoteConfiguration | Description | Default Value | Value Description & Examples |
---|---|---|---|
WAN | Radio technology used for connection to backend | lte |
|
Host | Hostname / IP of the Lobaro Platform API Not used for LoRaWAN uplink | 94.130.20.37 | 94.130.20.37 = platform.lobaro.com |
Port | Port number of the Lobaro Platform API Not used for LoRaWAN uplink | 5683 |
NB-IoT Parameters (WAN = "lte", "nbiot", "ltem")
The LTE functionality is enabled if the WAN
parameter is set to lte
, nbiot
, or ltem
. Using this mode requires an appropriate SIM-Card to be inserted.
Name | Description | Default Value | Value Description & Examples |
---|---|---|---|
Operator | Mobile Operator Code (optional) | 26201 | 26201 (=Deutsche Telekom), for other operators, see above. Empty = Auto detect (longer connecting time) |
Band | NB-IoT Band | 8 | "8", "20", "8,20", Empty = Auto detect (longer connecting time) |
APN | Mobile operator APN (optional) | iot.1nce.net | 1nce: iot.1nce.net Vodafone Easy Connect: lpwa.vodafone.com (l = littel L) |
PIN | SIM PIN (optional) | Empty or 4 digits (e.g. 1234 ) |
LoRaWAN Parameters (WAN = "lorawan", "lorawan-abp")
Name | Description | Default Value | Value Description & Examples | Since |
---|---|---|---|---|
DevEUI | DevEUI used to identify the Device | Device's own DevEUI as printed on label | 8 bytes = 16 hex digits, e.g. 0123456789abcdef | |
JoinEUI | EUI used for OTAA (aka AppEUI ) | Individual default value for each device | 8 bytes = 16 hex digits, e.g. 0123456789abcdef | |
AppKey | AES Key used for LoRaWAN | Individual default value for each device | 16 bytes = 32 hex digits, e.g. 0123456789abcdef001122334455667788 | |
SF | Minimal Spreading Factor used | 12 | 7-12 , used after reset, can be decreased by ADR during operation (but not increased) | |
OpMode | LoRaWAN Operation Mode | A | A = Class A, C = Class C | v0.2.1 |
...
Warning |
---|
Keep the value of |
OTAA - Over the Air Activation
The preferred method to use LoRaWAN is Over The Air Activation (OTAA). When WAN="lorawan"
the device uses the values to perform an OTAA Join with the LoRaWAN Network Server. Make sure the values for DevEUI, JoinEUI, and AppKey match.
...
Each Device will be configured with a unique JoinEUI and AppKey that are generated using a cryptographic hashing algorithm. Those values will seem random and are very likely to be unique for each device. These values are known to Lobaro but will not be made public. You can change the AppKey
if you prefere to have Keys that are known only to you. Be sure to use a good random source when generating keys.
ABP - Activation by personalisation
Our devices support activation by personalisation (ABP) when WAN="lorawan-abp"
. This mode is useful for devices that have a bad reception. You will have to synchronise session keys by hand between the device and your Network Server when using ABP.
...
The Values will be printed out in the Log after boot, so you can copy them to the configuration in your Network Server. Do change the DevAddr
, alter the DevEUI
value in the configuration. To create a different pair of session keys, change the value of AppKey
in the configuration. Best practise is, to change it to randomly generated bytes coming from a good random source. The generated Session Keys will be deterministic for a given value of AppKey
, even if used on different devices.
LAN Parameters (WAN = "lan")
Connection via LAN/Ethernet is not supported, yet.
Note |
---|
Coming soon! |
Modbus related Parameters
Name | Description | Default Value | Values Description & Examples |
---|---|---|---|
MbCmd | List of Modbus Commands with Cron and Modbus parameters (see below). | 0 0/5 * * * *:R,9600,8N1:010300000003 | One or more entries of Modbus commands to be executed by the device. Each entry starts with a Cron expression defining when to execute the commands followed by the bus parameters used to address the Modbus slave devices. Each entry can contain multiple commands. See description below for a detailed explanation. † |
...
Code Block | ||
---|---|---|
| ||
MbCmd = "<Entry1>;<Entry2>;...;<Entry32>" Entry = "<Cron>:<MbParm>:<Command1>,<Command2>,...,<CommandN>" MbParm = "<Protocol>,<Baud>,<SymbolCfg>" Protocol = "R" for Modbus RTC, "A" for Modbus ASCII Baud = Baud rate, any of: 2400, 4800, 9600, 19200, 38400, 57600, 115200 SymbolConfig = Token string defining Data Length, Parity, and Stop Bits. Any of: "7E1", "7E2", "8N1", "8N2" Command = "<bytes to be sent in hex without checksum>" |
Examples
Code Block |
---|
Example A: "0 0/5 * * * *:R,9600,8N1:010300000003" Entry 1: Cron: "0 0/5 * * * *": Execute entry every 5 minutes, on minutes 0, 5, 10, 15, ..., 55 Config: "R,9600,8N1": Use Modbus RTU on 9600 Baud, Datalength: 8, Parity: None, 1 stop bit Commands: "010300000003": Read 3 holding registers of Slave 1, starting at register 0 Example B: "0 * * * * *:A,9600,7E1:0e0400100004,0f400100004;0 0 * * * *:A,9600,7E1:0e0400200020" Entry 1: Cron: "0 * * * * *": Execute entry every full minute Config: "A,9600,7E1": Use Modbus ASCII on 9600 Baud, Datalength:7, Parity: Even, 1 stop bit Commands: "0e0400100004": Read 4 input registers of Slave 14, starting at register 16 "0f0400100004": Read 4 input registers of Slave 15, starting at register 16 Entry 2: Cron: "0 0 * * * *": Execute entry every full hour Config: "A,9600,7E1": Use Modbus ASCII on 9600 Baud, Datalength:7, Parity: Even, 1 stop bit "0e040a800020": Read 32 input registers of Slave 14, starting at register 2688 |
Modes of operation (work cycle)
Note |
---|
Subject to change! This product is still very young and experience might lead to adjustments in the future. |
This chapter explains how the device starts and works to collect and upload data.
Startup process
The starting process of the device is linear and executed the following steps in the order given here. The startup is triggered on power on or after a reset was triggered; this can happen over the reset button, by using the Lobaro tool over the config adapter, by sending a reboot command via Downlink, of if a fatal error occurs during operation of the device.
- On power on (or after a reset), the device will start by verifying the signature of the installed firmware. It will only continue the boot process if the signature is valid.
- The device will then activate the Arm TrustZone of its central processor, to prepare an isolated environment for the actual firmware to run. This activates hardware security mechanisms that protect the device from a wide range of errors and manipulations while it is running.
- Only then, the application program is started, having restricted access to the hardware.
- The application reads and outputs the configuration parameters programmed into it and verifies the configuration does not contain any obvious errors (like invalid syntax or impossible value combinations). If any fatal errors exist, the device will output information about it in the Log and then reboot, so that you spot invalid configurations directly when you set them.
- At this point the RGB-LED starts to continuously output the state of the Modbus connection and the connection to the backend.
- The device will try and execute every Modbus command from every entry in the configuration parameter
MbCmd
, using the Modbus configuration of the entry (writing operations are skipped to avoid side effects). This allows you to check your Modbus configuration and the connection to the slave devices early on boot and even without a config adapter attached. The device will continue execution, even if the Modbus Commands fail, so that you can check the connection to the backend even when not connected to the Modbus slaves. - After testing Modbus, the device will try to connect to the network for connection to the backend. The exact action will depend on your configuration:
- For NB-IoT or LTE-M the Gateway will activate its Modem and try to attach to the mobile provider. If that succeeds, it will try to connect to the backend configured (normally an instance of the Lobaro Platform). If that succeeds, the device will upload some information about itself to the backend (including its configuration) and than synchronise its internal clock over the connection. Only if all this succeeds, the device will move on.
- For LoRaWAN with OTAA, the device will perform an OTAA Join operation with the LoRaWAN Network Server. If that succeeds, the device will upload a Status Message that will also be used to synchronise its internal clock with the network. Only if that succeeds, the device will move on. On failure, the device will retry with increasing timeouts to perform the join operation and time sync, until it succeeds.
- For LoRaWAN with ABP there is no explicit joining operation, as the session must already exist between Network Server and Device. It simply uploads a Status Message that will also be used to synchronise the internal clock. If the synching fails multiple times, the device will skip synchronisation and just move on to start normal operations. Be aware that this can lead to the Device operating with a clock that does not match real time. The Modbus Commands will be executed according to that clock, which will most likely not be consistent with what you expect. This exception is introduced on purpose, as ABP is meant to make the device usable in locations, where there is poor Downlink reception from the Network, where an OTAA Join cannot be performed, but Uplink messages still might be coming through to the Network. The device will continue to try and synchronise its clock every day and might succeed at some point in the future. The changing of the clock will be compensated as well as possible, but the exact times when commands are executed is most likely to change at that point.
- When the connection to the backend has been established (this is not certain to have succeeded when using LoRaWAN ABP), the device will start its internal scheduler and will from this moment on be running in normal operation mode.
Normal operation
The actions executed by the device during normal operation are controlled by a scheduler that executes a list of jobs whenever it is their time to run. Only a single job will be executed at any time, so if a job is running for some time, other jobs will be executed delayed (but the execution will not be skipped). Each entry you add to the MbCmd
config parameter will have its own job in the scheduler. The Cron Expression of the entry will control, how often and when the job will be executed. In addition to that there will be a Status job which runs once every day and triggers the upload of a status message which will also perform a clock synchronisation. When your configuration has multiple entries that are scheduled for the same time, they will be executed in the order you put them in the configuration.
...
Changing configuration or performing a firmware update will result in the Gateway rebooting. We try our best to keep our devices from ever reaching a state that makes them unreachable. A new configuration set via Downlink will be temporary until a connection to the Network can be established again. If the new configuration fails to connect to the Network, the previous configuration is restored.
Mobile data consumption
Uploading one Uplink with 400 bytes including all metadata (might be less, depending on the configuration).
...
All calculations are estimations and might vary depending on the configuration
The Lobaro Platform
The easiest way to work with the Lobaro Modbus Gateway is the Lobaro Platform. You can find it under https://platform.lobaro.com – Log in with the credentials provided by Lobaro.
Your Gateways should be listed under "Devices". If you have multiple devices in your account, you can distinguish them by the field "Address". The Address is printed on the box of the Gateway (the Address is the IMEI of the modem used by the device; that is the unique hardware address used for mobile communication).
Data messages
Data messages differ between LoRaWAN and LTE/LAN upload. While LoRaWAN messages are defined by Port and Byte pattern, LTE/LAN Uplinks are encoded as structured data (CBOR).
...
Note |
---|
Coming soon! For now please refer to our Modbus LoRaWAN Bridge - We try to keep the payloads similar. |
LoRaWAN Payload formats
The Modbus Bridge sends two different kinds of messages over different LoRaWAN ports:
Direction | Port | PlFmt Value | Message |
---|---|---|---|
Uplink | 1 | any | Status messages. |
Uplink | 3 | 1 | Modbus Responses triggered by configuration. |
Uplink | 4 | any | Modbus Responses triggered by Downlinks. |
Uplink | 5 | any | Continuation of Responses that do not fit in a single Uplink. |
Uplink | 20 | 4 | Compact payload format with timestamp |
Uplink | 20 | 5 | Compact payload format without timestamp |
Uplink | 128 | any | Remote configuration response |
Uplink | 129-131 | any | Remote configuration long response 129 = start, 130 = middle, 131 = last |
Downlink | 4 | any | Modbus Commands to be forwarded by the Bridge. |
Downlink | 128 | any | Remote configuration |
Uplink Messages
Status message (Port 1)
The Modbus Bridge sends a status messages report on the health of the device itself. This messages are sent along when the device is sending data packages with a maximum of one status message per day.
...
name | pos | len | type | description | example |
---|---|---|---|---|---|
version | 0 | 3 | uint8[3] | Version of firmware running on the device | [0, 4, 1] ≡ v0.4.1 |
flag | 3 | 1 | uint8 | Status flag, for internal use | 0 |
temperature | 4 | 2 | int16 | Device's internal temperature in tenth °C | 246 ≡ 24.6°C |
voltage | 6 | 2 | uint16 | Voltage supplied by power source in mV | 3547 ≡ 3.547V |
timestamp | 8 | 5 | int40 | Internal date/time at creation of the status packet as UNIX timestamp | 1533055905 |
plFmt | 13 | 1 | uint8 | The configured payload format | 1, 2, 3, 4, 5 |
resetReason‡ | 14 | 1 | uint8 | Cause of latest reset, coded | 0 |
finalWords‡ | 15 | 1 | uint8 | Last info before latest reset, coded | 0 |
‡ Since version 1.3.0.
Data messages - verbose format (Port 3, PlFmt=1)
Data messages contain responses to Modbus Commands received by the Bridge. The Bridge supports multiple Payload formats for different use cases. The format is selected by the configuration parameter PlFmt
:
...
Bytes | 0 | 1 .. len-3 | len-2 . len-1 | len |
+-----+-----------------+----------------+-------+
Field | len | Modbus response | start register | count |
Reference Decoder
This is a decoder written in JavaScript that can be used to parse the device's LoRaWAN messages. It can be used as is in The Things Network.
Expand | ||
---|---|---|
|
Compact Payload Format (Port 20, (21-59) PlFmt=4&5)
The Modbus Bridge provides an alternative Payload Format for uplinks that uses the limited bandwidth more efficiently by only sending data. This requires a dedicated parser on the network server of application server that has knowledge of the device's configuration. The configuration can be requested from devices in the field with our Remote Configuration. Be aware that Error Conditions cannot be communicated as well in this format.
...
Part | HD | response 1 | response 2 | ... | response n |
Response to Downlink (Port 4)
A Downlink Modbus Command can be executed on Downlink Port 4. The answer has the verbose payload format like described above on port 3.
...
For details about the downlink see below.
Split messages (Port 5)
If a single Modbus Response does not fit into a LoRaWAN uplink, due to the length restriction for the current Spreading Factor, the message is split up into multiple Uplinks. The first part will be sent on Port 3 (for cron triggered reads) or on Port 4 (for reads triggered by downlink). The remaining Bytes will be sent in the following uplinks on Port 5 in as many Uplinks as needed. You can know that an Uplink is split, when the length information (Byte 0 in the response part) is longer than the data following it. The payload from Port 5 must be appended to the last uplink received on either Port 3 or 4 in your application server, before you can parse the message. Check the frame counter to make sure you receive all parts. For very long responses and high Spreading Factors, splits over up to 6 messages are possible.
...
Expand | |||
---|---|---|---|
| |||
ExamplesThis chapter illustrates with some examples, how working with the Modbus Bridge looks like. The bytes that are sent via LoRaWAN are presented here as hex strings, while on the air they are sent as raw bytes. Modbus Commands and Responses are broken down to their parts in the explanations, but explaining the format used by Modbus in detail is beyond the scope of this manual. You can find a short explanation on Modbus on Wikipedia: https://en.wikipedia.org/wiki/Modbus. Uplinks in Verbose Payload Format (PlFmt=1)The following shows some examples of configuration for the automated reading and what the generated Uplinks for that could look like. Example A1: Read Holding Registers 0, 1, and 2 of device with address 1
Example A2: Read coils 1000-1019 of device 32
Example A3: Read registers from two devices
Example A4: Split uplink message
Uplinks triggered by Downlink CommandsExample B1: Read single Input Register by Downlink
Example B2: Writing holding registers on multiple devices
Uplinks in Compact Payload FormatExample C1: Single Modbus Command, PlFmt 4
Example C2: Multiple Commands, PlFmt 5
Example C3: Multimple Commands, leading in multiple Upoads, PlFmt 5
|
...
Direction | Port | PlFmt Value | Message |
---|---|---|---|
Uplink | 1 | any | Status messages. |
Uplink | 3 | 1 | Modbus Responses triggered by configuration. |
Uplink | 4 | any | Modbus Responses triggered by Downlinks. |
(Port 128 (129-131))
When Remote Configuration is enabled, you can send Downlinks on Port 128 to read or set Config Parameters and execute commands like Reboot. Responses to those Downlinks are set on port 128 (or 129-131 if they are too long for a single Uplink).
...
Note |
---|
The current Firmware does not support permanent saving after changing the configuration with a downlink. This configuration only persists until a reboot. A fix will be available soon. |
NB-IoT/LTE Payload formats
The Modbus Bridge sends different kinds of messages over different Querys ("q"):
"q": "device" (in first upload frame) Device description
"q": "config" (in second upload frame) Configuration description
"q": (still) does not exist (from the third package) normal data packages
Data Uplink Messages (part):
Code Block |
---|
{ "d": { "mb": [ { "cmd": "AQMAFgAC", "rsp": "AQMEAUEYeA==", "time": 1660050482, "error": 0 }, ] }, "i": "70b3d5e050011bb4", "n": 19 } |
"mb" modbus
"cmd" (command) "AQMAFgAC" is equivalent in HEX "010300160002"
SlaveID (01) Command Read (03) Register 0016 (dec 22) Quantity 0002 (2)
"rsp" (response) "AQMEAUEYeA==" is equivalent in HEX "01030401411878"
SlaveID (01) Command Read (03) Quantity Bytes (04) ValueRegister1+2 (01 41 18 78)
Equivalent Hex 01 41 in DEC is 321 (Example: if register 00 00 is the value for temperature/100 it represents 3,21 Grad Celsius)
"time" 1660050482 (UnixTimeStamp Tue Aug 09 2022 13:08:02 GMT+0000)
"error" 0 (no error)
"i" 70b3d5e050011bb4 (DevEUI)
"n" 19 (frame counter)