Code Block |
---|
{ "data": { "d": { "mb": [ { "cmd": "AQMAFgAC", "rsp": "AQMEAUEYeA==", "time": 1660050482, "error": 0 }, ] }, "i": "70b3d5e050011bb4", "n": 19 } } |
(modbus) "mb" modbus
"cmd" (command) "AQMAFgAC" is equivalent in HEX "010300160002"
SlaveID (01) Command Read (03) Register 0016 (dec 22) Quantity 0002 (2)
(modbus)
"rsp" (response) "AQMEAUEYeA==" is equivalent in HEX "01030401411878"
SlaveID (01) Command Read (03) Quantity Bytes (04) ValueRegister1+2 (01 41 18 78)
Equivalent Hex 01 41 in DEC is 321 (if register 00 00 is the value for temperature/100 represents 3,21 Grad Celsius)
"time" 1660050482 (UnixTimeStamp Tue Aug 09 2022 13:08:02 GMT+0000)
"error" 0 (no error)
"i" 70b3d5e050011bb4 (DevEUI)
"n" 19 (packet counter)
...