Revision 1.0 (03.2021)

Bild entspricht nicht der aktuellen Version! Sensorausführung an der kurzen Seite.

Technical characteristics
TypesLOB-S-HYB-1WIRE
DescriptionMulti Temperatur V2 (LoRaWAN, NB-IoT, 1m sensor)
Order number: 8000170 (LOB-S-HYB-1WIRE)
Order number (Variant): 

-

LoRaWAN Specifications
LoRaWAN ProtocolClass A  LoRaWAN 1.0.2 EU868
Activation methodOver-the-air activation (OTAA)
Activation by personalization (ABP)
Typically RF range≤ 2km
Ideal RF range≤ 10km (free line of sight)
TX Power≤ 14 dBm
Remote configurationsupported
NB-IoT Connectivity
LTE SiPNordic nRF9160
Antenna
  • Internal Monopole
  • On Request: External Antenna (SMA female)
Supported LTE Band
  • Standard: B8, B20, B3 (791 MHz - 969 MHz, 1710 MHz – 1785 MHz)
  • Other Bands on request
SIM card slot4FF (Nano SIM)
Supported LTE modes
  • Narrowband IoT (NB-IoT)
  • LTE Cat-M1  (on request)
Firmware Features
  • Remote configuration (via Lobaro IoT Platform)
  • Remote firmware update (via Lobaro IoT Platform)
I/O & Sensors
Internal Temperature Sensor1x internal
External 1-Wire temperature sensor busFor up to 25 additional 1-Wire DS18B20 temperature sensors. Connected in start or serial configuration 
Local configuration portPC based initial configuration via USB adapter
Internal LEDRGB Led to signal different operating modes
Power Supply
Supply Voltage ConnectionJST-XH connector
Nominal Supply Voltage3.6V
Supply Voltage Range3 - 3.6V
Power supplyLobaro ER34615M 3.6V primary battery (D-cell)
Current consumption @3.6V
Normal / Idle≤ 3 mA
LoRa RX≤14 mA
LoRa TX≤80 mA
Sleep with RTC running≤15 µA
Mechanical dimensions
Size130 mm x 82 mm x 55 mm (incl. pressure compensating element)
Weight220g (excl. Battery) + Battery: ca. 114g
Housing MaterialIndustrial polycarbonate
RatingIP66 including pressure compensating element
Environmental Requirements
Operating temperature range-20°C to +55°C
Max. Installation height2m
Conformity

 

  • EN 300 220-1 (RF)
  • EN 300 220-2 (RF)
  • EN 301 489-3 (EMC)
  • EN 62368-1 (Electrical Safety)
  • EN 62311:2008 (Electrical Safety)
  • EN 50581 (RoHS)


  • No labels