Lobaro Pressure and Temperature Sensor

To read out the pressure & temperature probe, the Hybrid Modbus Gateway must be configured as follows:

ParameterValueComment
WANlorawanFor LoRaWAN OTAA usage.
PlFmt5Sets the payload to a short format.
MbCmd0 0/5 * * * *:R,9600,8N1:010300160002,010300260002Reads the Registers 22-23 and 34-35. The CRON Expressions can be adjusted to set time of sensor reading.
PowerOnDelay1500Battery variant only. Sets time (in ms) between activating sensor power and reading value (time for sensor to be ready).

Data Uplink (Port 20)

Bytes | 0 .    | 1 . 2 . 3 . 4 . | 5 . 6 . 7 . 8 . |
------+--------+-----------------+-----------------+
Field | Header | Pressure | Temperature |
FieldTypeValue
Headeruint80x00 on success, 0x80 if an error occurred
Pressurefloat32Pressure in mH2O, ffffffff on error.
Temperaturefloat32

Temperature in °C, ffffffff on error.

Example

# Example of a successful measurement
'003d94ce4541b7a512'
  '00'       -> Successful readout
  '3d94ce45' -> 0.073 mH2O
  '41b7a512' -> 22.96 °C

# Example
'80ffffffffffffffff'
  '80'       -> An error occurred.
  'ffffffff' -> Pressure could not be read.
  'ffffffff' -> Temperature could not be read.

Reference Parser

see below

Lobaro Pressure Sensor

Reading from the Lobaro Pressure Sensor using the Hybrid Gateway can be done by setting the following parameters in the configuration:

ParameterValueComment
WANlorawanFor LoRaWAN OTAA usage.
PlFmt5Sets the payload to a short format.
MbCmd0 0/5 * * * *:R,9600,8N1:010300040001,fa0400040001Reads the register 4 inside probe and 4 inside Bridge. The CRON Expressions can be adjusted to set time of sensor reading.
PowerOnDelay1500Battery variant only. Sets time (in ms) between activating sensor power and reading value (time for sensor to be ready).

Data Uplink (Port 20)

Bytes | 0 .    | 1 . 2 .  | 3 . 4 .     |
------+--------+----------+-------------+
Field | Header | Pressure | Temperature |
FieldTypeValue
Headeruint80x00 on success, 0x80 if an error occurred
Pressureint16BE

Pressure in mmH2O

Temperatureint16BE Temperature in °C inside Bridge

Example

# Example of a successful measurement
'000211001a'
  '00'       -> Successful readout
  '0211' -> 529 -> 0.529 mH2O
  '001a' -> 26 -> 26°C (inside Box)

Reference Parser

Pressure Probe Parser
/**
 * Parser for Lobaro Pressure Probe via LoRaWAN (hybrid gateway).
 * Usable for Pressure Probe as or with Presure+Temperature Probe.
 * Works with TTN, ChirpStack, or the Lobaro Platform.
 */
function signed(val, bits) {
    // max positive value possible for signed int with bits:
    var mx = Math.pow(2, bits-1);
    if (val < mx) {
        // is positive value, just return
        return val;
    } else {
        // is negative value, convert to neg:
        return val - (2 * mx);
    }
}
function int16_BE(bytes, idx) {
    bytes = bytes.slice(idx || 0);
    return signed(bytes[0] << 8 | bytes[1] << 0, 2*8);
}
function uint16_BE(bytes, idx) {
    bytes = bytes.slice(idx || 0);
    return bytes[0] << 8 | bytes[1] << 0;
}
function uint32_BE(bytes, idx) {
    bytes = bytes.slice(idx || 0);
    return bytes[0] << 24 | bytes[1] << 16 | bytes[2] << 8 | bytes[3] << 0;
}
function float32FromInt(asInt) {
    var sign = (asInt & 0x80000000) ? -1 : 1;
    var exponent = ((asInt >> 23) & 0xFF) - 127;
    var significand = (asInt & ~(-1 << 23));
    if (exponent === 128)
        return null;
        // return sign * ((significand) ? Number.NaN : Number.POSITIVE_INFINITY);
    if (exponent === -127) {
        if (significand === 0) return sign * 0.0;
        exponent = -126;
        significand /= (1 << 22);
    } else significand = (significand | (1 << 23)) / (1 << 23);
    return sign * significand * Math.pow(2, exponent);
}
function float32_BE(bytes, idx) { return float32FromInt(uint32_BE(bytes, idx)); }

/**
 * TTN decoder function.
 */
function Decoder(bytes, port) {
    var vals = {};
    if( port == 20 ){
        if (bytes.length==5) {
          // Pressure Probe without temperature sensor and Bridges internal Temperature
	      vals["error"] = !!(bytes[0]&0x80);
          vals["pressure"] = int16_BE(bytes, 1)/1000;
          vals["temperature"] = int16_BE(bytes, 3);
        } else if (bytes.length==9) {
          vals["error"] = !!(bytes[0]&0x80);
          // pressure in mH2O
          vals["pressure"] = float32_BE(bytes, 1);
          // temperature in Degree Celsius
          vals["temperature"] = float32_BE(bytes, 5);
        }
    } 
    return vals;
}
 
/**
 * TTN V3 Wrapper
 */
function decodeUplink(input) {
   return {
    data: {
      values: Decoder(input.bytes, input.fPort)
    },
    warnings: [],
    errors: []
  };
} 
 
/**
 * ChirpStack decoder function.
 */
function Decode(fPort, bytes) {
    // wrap TTN Decoder:
    return Decoder(bytes, fPort);
}
 
/**
 * Lobaro Platform decoder function.
 */
function Parse(input) {
    var data = bytes(atob(input.data));
    var port = input.fPort;
    return Decoder(data, port);
}