ParameterValueComment
WANlorawanFor LoRaWAN OTAA usage.
PlFmt5Sets the payload to a short format.
MbCmd0 0/15 * * * *:R,9600,8N1:010300160002,010300260002,fa0400050001
  • 010300160002 - Read register 22-23 (pressure)
  • 010300260002 - Read register 38-39 (temperature)
  • FA0400050001 - Read internal register 5 (vBat)

The CRON Expressions can be adjusted to set time of sensor reading.

PowerOnDelay3000Battery variant only. Sets time (in ms) between activating sensor power and reading value (time for sensor to be ready).

Command (since FW v0.10.2)

Starting from v0.10.2 we support a command for LoRaWAN only!

ParameterValueComment
Cmd0 * * * * *:pressure(port=20)Special command to upload in same format but calculating a more stable pressure value

Modbus Register Mapping

The probe is a Modbus slave with the following registers:

...